Go to Network protocols > PROFINET > Data mapping.

Modules
  1. Go to Modules tab.

  2. To add a module, click button Add more modules.

    Modules tab
    Figure 35. Modules tab


  3. Enter the values for the module and the submodule:

    • Module ID: 0x00000001

    • Module name: InputModule

    • Submodule ID: 0x00000001

    • Submodule name: InputSubmodule

    • Cyclic data set, Input: InputDataSet

    • Cyclic data set, Output: -

    • Virtual: ✓

  4. Click button + in the module row to repeat step 3 with the following values:

    • Module ID: 0x00000002

    • Module name: OutputModule

    • Submodule ID: 0x00000001

    • Submodule name: OutputSubmodule

    • Cyclic data set, Input: -

    • Cyclic data set, Output: OutputDataSet

    • Virtual: ✓

  5. Click button Apply.

    PROFINET Modules example

    PROFINET Modules example

    Figure 36. PROFINET Modules example


The Device Access Point (DAP) module is predefined and cannot be changed. See Device Access Point (DAP).

Slots
  1. Go to Slots tab.

  2. To add a slot and assign module, click button Add more slots.

    Slots tab
    Figure 37. Slots tab


  3. Enter the values for the slot:

    • Slot number: 0x0001

    • Name: Input Slot

    • Module in slot: InputModule

    • Plugging rule: Fixed in

  4. Click button + and repeat step 3 with the following values:

    • Slot number: 0x0002

    • Name: Output Slot

    • Module in slot: OutputModule

    • Plugging rule: Fixed in

  5. Click button Apply.

    PROFINET Slots example

    PROFINET Slots example

    Figure 38. PROFINET Slots example


The Device Access Point (DAP) slot is predefined and cannot be changed. See Device Access Point (DAP).

Subslots
  1. Go to Sublots tab.

  2. Enter the values for the subslots in the InputModule:

    • Subslot number: 0x0001

    • Subslot name: InputSubslot

    • Submodule in subslot: InputSubmodule

  3. Repeat step 2 with the values for the OutputModule:

    • Subslot number: 0x0001

    • Subslot name: OutputSubslot

    • Submodule in subslot: OutputSubmodule

  4. Click button Apply.

    PROFINET Subslots example

    PROFINET Subslots example

    Figure 39. PROFINET Subslots example


Identification
  1. Go to Network protocol > PROFINET > Device identification.

  2. Use default values unless specified:

    Identification setting

    Data type

    Source type

    Source / Constant value

    Vendor ID

    UINT16

    Constant

    268

    Vendor name

    STRING

    Constant

    HMS

    Device ID

    UINT16

    Constant

    38

    Product family

    STRING

    Constant

    EVK Demo

    Order ID

    STRING

    Constant

    My Order Number

    Hardware revision

    UINT16

    Constant

    0

    Software revision

    UINT32

    Constant

    256

    Serial number

    UINT32

    Built-in

    Managed internally

  3. Click button Apply.

    PROFINET Identification example

    PROFINET Identification example

    Figure 40. PROFINET Identification example


To do next

Download configuration files and signing tool, see Finalize the configuration .