Configure PROFINET - Modbus RTU
Go to Network protocols > PROFINET > Data mapping.
Modules
Go to Modules tab.
To add a module, click button Add more modules.
Figure 35. Modules tabEnter the values for the module and the submodule:
Module ID: 0x00000001
Module name: InputModule
Submodule ID: 0x00000001
Submodule name: InputSubmodule
Cyclic data set, Input: InputDataSet
Cyclic data set, Output: -
Virtual: ✓
Click button + in the module row to repeat step 3 with the following values:
Module ID: 0x00000002
Module name: OutputModule
Submodule ID: 0x00000001
Submodule name: OutputSubmodule
Cyclic data set, Input: -
Cyclic data set, Output: OutputDataSet
Virtual: ✓
Click button Apply.

PROFINET Modules example
Figure 36. PROFINET Modules example
The Device Access Point (DAP) module is predefined and cannot be changed. See Device Access Point (DAP).
Slots
Go to Slots tab.
To add a slot and assign module, click button Add more slots.
Figure 37. Slots tabEnter the values for the slot:
Slot number: 0x0001
Name: Input Slot
Module in slot: InputModule
Plugging rule: Fixed in
Click button + and repeat step 3 with the following values:
Slot number: 0x0002
Name: Output Slot
Module in slot: OutputModule
Plugging rule: Fixed in
Click button Apply.

PROFINET Slots example
Figure 38. PROFINET Slots example
The Device Access Point (DAP) slot is predefined and cannot be changed. See Device Access Point (DAP).
Subslots
Go to Sublots tab.
Enter the values for the subslots in the InputModule:
Subslot number: 0x0001
Subslot name: InputSubslot
Submodule in subslot: InputSubmodule
Repeat step 2 with the values for the OutputModule:
Subslot number: 0x0001
Subslot name: OutputSubslot
Submodule in subslot: OutputSubmodule
Click button Apply.

PROFINET Subslots example
Figure 39. PROFINET Subslots example
Identification
Go to Network protocol > PROFINET > Device identification.
Use default values unless specified:
Identification setting
Data type
Source type
Source / Constant value
Vendor ID
UINT16
Constant
268
Vendor name
STRING
Constant
HMS
Device ID
UINT16
Constant
38
Product family
STRING
Constant
EVK Demo
Order ID
STRING
Constant
My Order Number
Hardware revision
UINT16
Constant
0
Software revision
UINT32
Constant
256
Serial number
UINT32
Built-in
Managed internally
Click button Apply.

PROFINET Identification example
Figure 40. PROFINET Identification example
To do next
Download configuration files and signing tool, see Finalize the configuration .