Skip to main content

Anybus® ONE™ Developer Portal

Hardware overview and connections

An overview of the Evaluation Board, including its hardware, connectors, and status indicators.

Evaluation Board hardware overview

Important

Some components and board positions on the Evaluation Board are reserved for future use and are not populated or supported in the current release.

Evaluation Board components
Figure 3. Evaluation Board components


  1. Modbus RTU 5‑pin screw terminal

  2. USB-C connector for debug

  3. Reset button

  1. SPI Interface

  2. Anybus ONE System on Module (SoM)

  3. Ethernet connector for PROFINET, Port 2

  1. Ethernet connector for PROFINET, Port 1

  2. Power switch

  3. Power 3-pin connector

SPI Interface
ao-evk_SPI_pinout.png

Pin

Signal

7

Serial Clock (SCK)

8

Chip Select (CS)

9

Master output, slave input (MOSI)

10

Master input, slave output (MISO)

19

GND

20

GND

Modbus RTU connector pinout
5pin-connector-mrtu.png
Table 1. 5-pin connector

Pin

Signal

1

ISO_5V

2

RS485_B (+)

3

RS485_A (-)

4

ISO_GND

5

Shield



Network and Modules status LED indicators
Network (NS )and Modules (MS) status LED indicators
Figure 4. Network (NS )and Modules (MS) status LED indicators


Position

LED

Color

State

Description

A

-

-

-

Reserved for future features

B

-

-

-

Reserved for future features

C

Network Status (NS)

Off

-

No IP address configured or no power

Red

Steady ON

Fatal error, MS also steady red

Red

Steady ON

Duplicate IP address

Red

Blinking 1 Hz

IO connection timeout

Green

Blinking 1 Hz

Identification signal active (DCP Control/Signal), MS also blinking green

Green

Blinking 1 Hz

IP address configured, no IO connection, or IO connection in a bad state

Green

Steady ON

IP address configured and IO connection established (at least one IO channel open, all IO channels OK)

D

Module Status (MS)

Off

-

No power

Red

Steady ON

Fatal error, NS also steady red

Red

Steady ON

Configuration error

Red

Blinking 1 Hz

Internal error

Green

Blinking 1 Hz

Identification signal active (DCP Control/Signal), NS also blinking green

Green

Steady ON

Module healthy and configured

Power-up test sequence (initialization): After power-up, before normal indication begins, the MS and NS indicators will perform a power-up test sequence.

Ethernet RJ45 LED indicators
LED A. Link/Activity LED B. Not used
Figure 5. LED A. Link/Activity LED B. Not used


State

LED A - Function

LED B - Function

Off

No link (or no power)

Not used

Green

Link (100 Mbit/s) established

Green, flashing

Activity (100 Mbit/s)

Yellow

Link (10 Mbit/s) established

Yellow, flashing

Activity (10 Mbit/s)