Configure Modbus RTU
Go to Host interface > Modbus RTU.
Parameters
Go to Parameters tab.
Click button Add parameters to Holding Registers to add four Holding registers.

Use these values:
Direction
Address
Name
Data Type
Access
Default
Modbus RTU → PROFINET
0x123
InputParam1
UINT16
R
-
Modbus RTU → PROFINET
0x124
InputParam2
UINT16
R
-
PROFINET → Modbus RTU
0x125
OutputParam1
UINT16
R/W
0x2222
PROFINET → Modbus RTU
0x126
OutputParam2
UINT16
R/W
0x2223
Click button Apply.

Modbus RTU Parameters example
Figure 26. Modbus RTU Parameters example
Data sets
The host interface needs two data sets: one for input data and one for output data.
Go to Data sets tab.
To create a data set for the InputData, click button New Data Set.
Figure 27. Data sets tabEnter the following values:
Data set name: InputDataSet
Access type: Cyclic and acyclic
Direction: Input
Add parameters: InputParam1, InputParam2
To save the data set, click button Apply data set.
To create a data set for the OutputData, click button New Data Set.
Enter the following values:
Data set name: OutputDataSet
Access type: Cyclic and acyclic
Direction: Output
Offline action: Use default values
Add parameters: OutParam1, OutputParam2
To save the data set, click button Apply data set.

Modbus RTU Data sets example
Figure 28. Modbus RTU Data sets example
Settings
Go to Settings tab
Configure the communication settings:
Modbus Node ID: 1
Register order: Most significant register first
Bit rate (bps): 115 200
Parity & stop bits: E1 (even parity, 1 stop bit)
Timeout (ms): 500
Retries: 2
Click button Apply.

Modbus RTU Settings example
Figure 29. Modbus RTU Settings example
To do next
Configure PROFINET for Modbus RTU, see Configure PROFINET - Modbus RTU.